Financial sector

Date: November 14, 2007
Company: Financial sector
Cost Savings: £31,134 per annum
Services: Energy surveys

The client was a company in the financial sector occupying a purpose built office block in Central London with a total floor area of 4,087m2. The object of the energy survey was to identify areas where energy use could be reduced therefore reducing costs and carbon emissions.

The site uses electricity and has an oil fired boiler for heating/air conditioning where individual areas are maintained by Versatemp heat pumps.

The official benchmark for a building of this type is between 350 and 570 kWh/m2, the client was using 699 kWh/m2 which is poor and merited urgent investigation.

Our consultant noticed the boiler was working unnecessarily during a hot day.

On closer inspection it was noted that the main control valve indicated that it was in the full by-pass however, the valve was actually in full supply. The consequence of this action was the cooling tower wasting heat as quickly as the boiler provided it!

An isolation valve was shut to prove the assertion and that single action resulted in a 90% saving in oil used where the weekly consumption was reduced from over 300 gallons to just 30 gallons. This was an immediate saving of about £300 per week; the valve repair cost was £1,200 giving a 4 week payback.

In addition, the building is centrally air conditioned by an air handling unit (AHU) that has no provision for heat recovery to recover the waster heat.

It was recommended to look at ways for air recirculation or heat recovery, the cost of remedying the situation could be offset against Corporation Tax through Enhanced Capital Allowances (ECA). Also, the need to look at variable speed drives for the air con fans was highly recommended to further reduce energy used. Again, the cost of implementing the changes could be offset against ECA’s.

Below is a summary of the main recommendations:

  • Improve the boiler/cooling tower/Versatemp operation
  • Review the site’s electrical base load
  • Create an energy policy and awareness campaign
  • Improve BMS controls
  • Heat recovery
  • Add variable speed drives
  • If actioned, the recommendations would lead to
  • an annual saving of £31,134
  • an overall payback of 15 months
The client did action most of the recommendations and has reaped the benefits subsequently.

 

Energy surveying Financial sector energy survey
Contact Efficiency Direct
contact us now

Contact us to see how we can help your business to meet and exceed government regulations and save your company costs with energy

Latest energy news:
CRC Registration Date Looming, Be Warned !

A top City consultancy has cautioned businesses who still have not registered for the Carbon Reduction Commitment Energy Efficiency Scheme (CRC) to do so by the earlier date of 2nd Sep...

Businesses to see early benefits from smart meters

The Government and energy regulator Ofgem have published the long-awaited joint smart metering “prospectus”.

The document, published late July, set out proposals for how smart...

carbon trust safe contractor energy institute affiliations back to top